| Alerton | BACtalk | | HVAC | BACnet® | BACnet/IP or BACnet/e | Verify the data link used on your network (BACnet/IP or BACnet Ethernet). Alerton controllers can be setup as either one. | www.alerton.com |
| American Auto-Matrix | AspectFT Matrix Controller | | HVAC | BACnet® | BACnet/IP | Literature says BACnet/IP compatible. Need to verify if it is a server or client. | Matrix.asp |
| American Auto-Matrix | Integra | IT-500,IT-600 | HVAC | BACnet® | BACnet/IP | Tridium AX Device: Must have the optional BACnet/IP drivers installed. | integra.asp |
| Andover | Continuum | | HVAC | BACnet® | BACnet/IP | Not sure if BACnet/IP is a native option? | andover_continuum.xml&f=NNM1:Building+Management+System%7E%21NNM2:Building+Management+Systems%7E%21NNM3:Andover+Continuum |
| Automated Logic Corporation | WebCTRL® | | HVAC | BACnet® | BACnet/IP | All ALC controllers are native BACnet, however, you need to make sure the control points are exposed to BACnet/IP | webctrl |
| Blackboard | Transact | | Door Access | Not Supported | | No API available. | Access-Control.aspx |
| Brivo | ACS | | Security | Home | ? | Under review | products |
| BuildingLogix | Building Pro | | HVAC | BACnet® | BACnet/IP | Tridium AX platform - verify if BACnet/IP option is standard | Home |
| Can2Go | GW1 | | Gateway | BACnet® | BACnet/IP + Zigbee or EnOcean | This is a BACnet gateway to Zigbee and EnOcean wireless technologies | gateways.htm |
| Carrier | i-VU Open Standard/Plus | | HVAC | BACnet® | BACnet/IP | | 0,3068,CLI1_DIV12_ETI12678_MID6118,00.html |
| Carrier | I-Vu CCN, CCN+ | | HVAC | Not Supported | CCN (Proprietary) | You must use a CCN to BACnet/IP gateway like the I-Vu Integrator or I-Vu Link products. | 1,3059,CLI1_DIV12_ETI434_PRD1444,00.html |
| Carrier | i-VU CCN Link | | Gateway | BACnet® | BACnet/IP | This device can be added to i-VU CCN networks to allow BACnet | 1,3059,CLI1_DIV12_ETI434_PRD1660,00.html |
| Continental Access | CA3000 | | Security | Custom | CA Interaccess API interface | DoorOperation and RelayOperation commands available. | cicaccess.com |
| Control Solutions | Babel Buster BB2-7040 | BACnet to Zigbee Gateway | Gateway | BACnet® | BACnet/IP, Zigbee | BACnet gateway and Zigbee Coordinator for integration to Zigbee networks | BB2-7040.html |
| Control Solutions Inc. | Babel Buster IP/XL | | Gateway | BACnet® | LonWorks to BACnet/IP | | BBIPXL.html |
| Daikin | D-BACS | DMS502B51 (Bacnet) | HVAC | BACnet® | BACnet/IP | | products-units-and-controls.asp?sec=products&page=55 |
| Delta | DSC Controllers | | HVAC | BACnet® | BACnet/IP | | system-controllers |
| Delta | ASM-24E Access System Manager | | Security | BACnet® | BACnet/IP | | access |
| Distech Controls | EC-NET/EC-BOS | | HVAC | BACnet® | BACnet/IP | Same as Tridium - must have the BACnet/IP server option | Building_automation_system.html |
| DSX Access Control | DSX | | Security | Custom | ? | Vague direction on what needs to be done, but looks like it's possible. May need extra config and hardware to work. | www.dsxinc.com |
| Ecobee | Smart Thermostat | | Thermostat | BACnet® | WIFI + Zigbee? | Might be able to use a BACnet/IP to Zigbee gateway. Still under review. | smart-overview |
| FieldServer | Quickserver FS-QS-1011-0131 | | Gateway | BACnet® | LONWorks to BACnet/IP | | QuickServer.php |
| GE | A-Series Lighting Controller | | Lighting | BACnet® | BACnet/IP | | Dispatcher?REQUEST=PRODUCTS&id=remote_ope |
| HAI | OmniPro II, IIe, LT | | HVAC | Custom | ? | API is available. This controller supports lighting, loads, t-stats, and security | OmniOverview.asp |
| Honeywell | EBI | | HVAC | BACnet® | BACnet/IP | Must purchase the BACnet/IP server option | www.honeywell.com |
| Honeywell | Excel 5000 | | HVAC | Not Supported | C-Bus | Must use Honeywell EBI server w/ BACnet/IP option | www.honeywell.com |
| Honeywell | ComfortPoint | | HVAC | BACnet® | BACnet/IP | Tridium Niagara AX platform: Verify if BACnet server driver is included. | HoneywellComfortPoint?WT.ti=Honeywell+ComfortPoint |
| Honeywell | WEBs–AX™ | | Software | BACnet® | BACnet/IP | Needs BACnet server option. | WEB-S-AX#ProductSpecification |
| Honeywell | WEB-600 | | HVAC | BACnet® | BACnet/IP | Tridium Niagara product: Needs BACnet/IP server driver | WEB-600 |
| ISONAS | Isonas BACnet Gateway | | Security | BACnet® | BACnet/IP | | www.isonas.com |
| Johnson Controls | Metasys PMI | 12.x | HVAC | Custom | DDE | Can be done, but product line has been discontinued. | www.johnsoncontrols.com |
| Johnson Controls | Metasys MSEA | 1.x - Current | HVAC | JCI MSEA | SOAP/XML, MSSDA | Must install MSSDA component | www.johnsoncontrols.com |
| Johnson Controls | P2000 | 3.8 + | Security | JCI P2000 | XML-RPC | | www.johnsoncontrols.com |
| Johnson Controls | MSEA NAE/NIE | | HVAC | BACnet® | BACnet/IP | Devices must be enabled for BACnet/IP | www.johnsoncontrols.com |
| KanTech | Entrapass Access Control Software | Corporate or Global Edition | Security | Custom | TCP/IP | Requires custom interface using Smartlink.DLL. | software_entrapass.aspx |
| KMC | BACnet Controllers | | HVAC | BACnet® | BACnet/IP | Not supported w/ KMDigital products | www.kmccontrols.com |
| Lighting Control & Design | Link-To Building Automation (BACnet) | GR2400 L2 | Lighting | BACnet® | BACnet/IP | This is a gateway for access to remote and master lighting panels. | overview.asp?p=l2ba |
| Loytec | L-DALI | | Lighting | BACnet® | BACnet/IP | Gateway for DALI lighting | index.php?option=com_content&task=view&id=56&Itemid=151 |
| Loytec | LGATE-900 | | Gateway | BACnet® | LON, BACnet/IP, BACnet MS/TP | Gateway for LON | index.php?option=com_content&task=view&id=51&Itemid=18 |
| Lutron | GRAFIK 5000/6000/7000 | EM-A-BAC-IP-120 | Thermostat | BACnet® | BACnet/IP | This is an optional interface to the system. | ProductSpecification.aspx |
| Millennium Group | Millennium Expert | | Security | Not Supported | Proprietary | No public API available. | default.asp?LINKNAME=MILLENIUM_EXPERT |
| NetworkThermostat | Net/X | | Thermostat | NetworkThermostat™ | TCP | | www.networkthermostat.com |
| Novar | Logic One | | HVAC | Not Supported | Proprietary | | www.novar.com |
| Proliphix | NT Series | | Thermostat | Proliphix NT | HTTP | This product has been discontinued by Proliphix. | www.proliphix.com |
| Proliphix | IMC Series | | Thermostat | Not Supported | ? | No public API. Have heard that the NT API still works on this product, but that has not been confirmed. | www.proliphix.com |
| Schlage | Security Management Server | Enterprise 5.3.8 | Security | Custom | API will be release at v5.3.8. | Under review.... | software.asp |
| Siemens | APOGEE MEC/MBC Controllers | | HVAC | BACnet® | BACnet/IP | Web site info is confusing whether APOGEE network is BACnet/IP. MEC/MBC controllers appear to be BACnet/IP. Verify with your facility HVAC department. | www.siemens.com |
| Siemens | TALON for BACnet | 3.10 | HVAC | BACnet® | BACnet/IP | TALON also has a LON version which is not compatible. | bacnet.aspx |
| Siemens | Apogee Insight | 3.10+ | Other | BACnet® | BACnet/IP | BACnet Client/Server on the Insight workstation | index.php?m=23&p=88 |
| Siemens | PCX Compact for BACnet | 3.2.2 | HVAC | BACnet® | BACnet/IP | | index.php?m=23&p=388 |
| Solidyne | i3 | | HVAC | Custom | HTTP | | www.solidyne.com |
| Solidyne | InetSupervisor | | HVAC | Custom | XML/SOAP | | www.solidyne.com |
| Staefa | TALON | | HVAC | BACnet® | BACnet/IP and LON available | See Siemens TALON. Only BACnet supported. | |
| Staefa | Smart II | | HVAC | Not Supported | Proprietary | Need to integrate using Staefa Talon or a BACnet gateway product | |
| Synergy Lighting Controls | Synergy | SYBPC MLX | Lighting | BACnet® | BACnet | Verfify if link is BACnet ethernet or BACnet/IP. | family1.aspx?family=SYBPC |
| Synergy Lighting Controls | SYSC MLX | | Lighting | BACnet® | BACnet/IP | | family1.aspx?family=SYSC |
| TAC | I/A Series | UNC 410,520 Controllers | HVAC | BACnet® | BACnet/IP | This is a Tridium AX platform. | tac_i_a_series.xml# |
| TAC | I/A Series | MNB-1000 | HVAC | BACnet® | BACnet/IP | MicroNet controller w/ builtin BACnet router capability | tac_i_a_series.xml# |
| TAC | Vista | | HVAC | Custom | LON | | tac_vista.xml&p_function_id=23&p_family_id=17901&p_range_id=2312&f=F13%3ABuildings%7E%21NNM1%3ABuilding+Management+System%7E%21NNM2%3ABuilding+Management+Systems~!NNM2:Building+Management+Systems~!NNM3:TAC+Vista |
| TCS Basys | Ubiquity | | HVAC | Not Supported | proprietary | | features.php?pn=ubiquity |
| TCS Basys | Ubiquity QD2040 | | Gateway | Not Supported | proprietary | BACnet version is supposedly coming? | features.php?pn=qd2040-reg |
| Teletrol | eBuilding Network Controller | | HVAC | BACnet® | BACnet/IP | | owner_solutions_eBuilding.html# |
| Trane | Tracer Summit | | HVAC | BACnet® | BACnet/IP | Workstation and BCU are BACnet/IP | www.trane.com |
| Trane | Tracer SC | | HVAC | BACnet® | BACnet/LON | Not sure if this is BACnet/IP or not | www.trane.com |
| Trane | BCU | V16+ | HVAC | BACnet® | BACnet/IP | Building Controller | www.trane.com |
| Trane | Tracker | V12 | HVAC | Custom | LON | Need to confirm, but appears to be LON interface. May be other options to link to BACnet controllers. | www.trane.com |
| Tridium | Niagara AX - JACE | | HVAC | BACnet® | BACnet/IP | JACE or Workstation software must have BACnet/IP server option | www.tridium.com |
| Tyco | C-CURE | | Security | Custom | ? | Under review | software_CCURE800.aspx |
| Wattstopper | Weblink | | Gateway | BACnet® | BACnet | Network appliance for allowing LIC lighting panels to talk via BACnet | details.html?id=260&category=137&type=Commercial |
| Wattstopper | LICxx Lighting Panels | | Lighting | BACnet® | Proprietary | Must use Weblink network device to convert to BACnet | details.html?id=255&category=137&type=Commercial |
| Wattstopper | LIBxx Lighting Panels | | Lighting | BACnet® | BACnet MS/TP | These panels must be terminated in a controller that supports BACnet/IP | details.html?id=270&category=139&type=Commercial |
| XCI | ? | | Thermostat | NetworkThermostat™ | TCP | Should use same API as NetworkThermostat | www.xcicontrols.com |
| Yale | Real Living | | Door Access | Custom | Zigbee Wireless | Needs further investigation. | |